Rockwall |
Code of Ordinances |
Chapter 10. BUILDINGS AND BUILDING REGULATIONS |
Article III. BUILDING CODE |
§ 10-117. Amendments.
The following sections, paragraphs, and sentences of the International Building Code, 2015 edition, are hereby amended to read as follows:
Section 101.4; change to read as follows:
101.4 Referenced codes. The other codes listed in Sections 101.4.1 through 101.4.8 and referenced elsewhere in this code, when specifically adopted, shall be considered part of the requirements of this code to the prescribed extent of each such reference. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the Electrical Code shall mean the Electrical Code as adopted.
Section 101.4.4; change to read as follows:
101.4.4 Property maintenance. The provisions of the Rockwall Property Maintenance Code shall apply to existing structures and premises; equipment and facilities; light, ventilation, space heating, sanitation, life and fire safety hazards; responsibilities of owners, operators and occupants; and occupancy of existing premises from occupancy or operation.
Section 101.4.8; add the following:
101.4.8 Electrical. The provisions of the Electrical Code shall apply to the installation of electrical systems, including alterations, repairs, replacement, equipment, appliances, fixtures, fittings and appurtenances thereto.
Section 102.6; change to read as follows:
102.6 Existing structures. The legal occupancy of any structure existing on the date of adoption of this code shall be permitted to continue without change, except as otherwise specifically provided in this code, the International Existing Building Code, the Rockwall Property Maintenance Code or the International Fire Code.
Section 102.6.2; change to read as follows:
102.6.2 Buildings previously occupied. The legal occupancy of any building existing on the date of adoption of this code shall be permitted to continue without change, except as otherwise specifically provided in this code, the International Fire Code or Rockwall Property Maintenance Code, or as is deemed necessary by the building official for the general safety and welfare of the occupants and the public.
Section 103.3; change to read as follows:
103.3 Deputies. In accordance with the prescribed procedures of this jurisdiction and with the concurrence of the appointing authority, the building official shall have the authority to appoint a deputy building official, the related technical officers, inspectors, plan examiners and other employees. Such employees shall have powers as delegated by the building official. For the maintenance of existing properties, see the Rockwall Property Maintenance Code.
Section [A] 104.2.1 Determination of substantially improved or substantially damaged existing buildings and structures in flood hazard areas; delete
Section 104.10.1 Flood hazard areas. Delete.
Section 105.2; change "Building" to read as follows:
Building:
7.
Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work.
9.
Prefabricated swimming pools accessory to a Group R-3 occupancy that are less than 24 inches (610 mm) deep, do not exceed 5,000 gallons (18 925 L) and are installed entirely above ground.
11.
Swings and other playground equipment accessory to detached one- and two-family dwellings.
13.
Movable fixtures, cases, racks, counters and partitions not over 5 feet 9 inches (1753 mm) in height.
Section 110.3.5 Lath, gypsum board and gypsum panel product inspection. Delete exception.
Section 113; change title to read as follows:
SECTION 113 - Construction Advisory and Appeals Board
Section 113.1; change to read as follows:
113.1 General. The Construction Advisory and Appeals Board shall be in accordance with Article II, Division 3, Chapter 10 of the Code of Ordinances, City of Rockwall.
Section 202; amend definition of Ambulatory Care Facility as follows:
AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing or similar care on a less than 24-hour basis to individuals who are rendered incapable of self-preservation by the services provided. This group may include but not be limited to the following:
-Dialysis centers
-Sedation dentistry
-Surgery centers
-Colonic centers
-Psychiatric centers
Section 202; add definition of "Repair Garage" as follows:
REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement and other such minor repairs.
Section 202; add definition of "Self Storage Facility" as follows:
SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis.
Section 202; amend definition of SPECIAL INSPECTOR to read as follows:
SPECIAL INSPECTOR. A qualified person employed or retained by an approved agency who shall prove to the satisfaction of the registered design professional in responsible charge and the Building Official as having the competence necessary to inspect a particular type of construction requiring special inspection.
Section 202; amend definition to read as follows:
HIGH-RISE BUILDING. A building with an occupied floor located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access.
Section 403.1, Exception 3; change to read as follows:
3.
The open air portion of a building. [remainder unchanged]
Section 403.3, Exception; delete item 2.
Section 406.3.5 Carports; delete exception:
406.3.5 Carports. Carports shall be open on at least two sides. Carport floor surfaces shall be of an approved noncombustible material. Carports not open on at least two sides shall be considered a garage and shall comply with the requirements for private garages…
Section 406.3.5.1 Carport separation; add sentence to read as follows:
A fire separation is not required between a Group R-2 and U carport provided that the carport is entirely open on all sides and that the distance between the two is at least 10 feet (3048 mm).
Section 501.2; delete text:
Section 501.2; add section to read as follows:
501.2 Address identification. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property and from all rear alleyways / access. Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. These numbers shall contrast with their background; color selection shall accommodate all lighting conditions. Address numbers shall be Arabic numbers or alphabetical letters. Street address numbers shall be a minimum of 12 inches high with a minimum stroke width of 0.5 inch (12.7 mm). Unit/suite/apartment/rear/alley numbers shall be a minimum of 4 inches high. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure.
Exception:
Structures located within the historic district may utilize numbers a minimum of 6 inches high, as approved by the fire code official.
Section 903.2.9; add Section 903.2.9.3 to read as follows:
[F] 903.2.9.3 Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities.
Exception: One-story self-storage facilities that have no interior corridors.
Section 903.2.10; change to read as follows:
[F] 903.2.10 Group S-2 enclosed parking garages. An automatic sprinkler system shall be provided throughout buildings classified as enclosed parking garages in accordance with Section 406.4 of the International Building Code or where located beneath other groups.
Section 903.3.1.2.3; add section to read as follows:
[F] Section 903.3.1.2.3 Attics and Attached Garages. Sprinkler protection is required in attic spaces of such buildings three or more stories in height, in accordance with NFPA 13 and/or NFPA 13R requirements, and attached garages.
Section 903.3.1.4; add to read as follows:
[F] 903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be in accordance with the requirements of the applicable referenced NFPA standard and this section.
903.3.1.4.1 Attics. Only dry-pipe, preaction, or listed antifreeze automatic fire sprinkler systems shall be allowed to protect attic spaces.
Exception: Wet-pipe fire sprinkler systems shall be allowed to protect non-ventilated attic spaces where:
1.
The attic sprinklers are supplied by a separate floor control valve assembly to allow ease of draining the attic system without impairing sprinklers throughout the rest of the building, and
2.
Adequate heat shall be provided for freeze protection as per the applicable referenced NFPA standard, and
3.
The attic space is a part of the building's thermal, or heat, envelope, such that insulation is provided at the roof deck, rather than at the ceiling level.
Section 903.3.5; add a second paragraph to read as follows:
[F] Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every water-based fire protection system shall be designed with a 5 psi safety factor.
Section 903.4; add a second paragraph after the exceptions to read as follows:
[F] Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering.
Section 903.4.2; add second paragraph to read as follows:
[F] The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection.
Section 905.2; change to read as follows:
[F] 905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low alarm.
Section 905.3; add Section 905.3.9 and exception to read as follows:
[F] 905.3.9 Buildings exceeding 10,000 sq. ft. In buildings exceeding 10,000 square feet in area per story and where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access, Class I automatic wet or manual wet standpipes shall be provided.
Exceptions:
1.
Automatic dry and semi-automatic dry standpipes are allowed as provided for in NFPA 14.
2.
R-2 occupancies of four stories or less in height having no interior corridors.
Section 905.4; change Item 1., 3., and 5. and add Item 7. to read as follows:
[F] 1. In every required exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official.
2. {No change.}
3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Exception: Where floor areas adjacent to an exit passageway are reachable from an exit stairway hose connection by a … {No change to rest.}
4. {No change.}
5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3- percent slope), each standpipe shall be provided with a two-way hose connection located to serve the roof or at the highest landing of an exit stairway with stair access to the roof provided in accordance with Section 1011.12.
6. {No change.}
7. When required by this Chapter, standpipe connections shall be placed at two hundred feet (200') intervals along major corridors thereafter, or as otherwise approved by the fire code official.
Section 905.9; add a second paragraph after the exceptions to read as follows:
[F] Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering.
Section 907.1; add Section 907.1.4 to read as follows:
[F] 907.1.4 Design standards. Where a new fire alarm system is installed, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog initiating devices.
Section 907.2.1; change to read as follows:
[F] 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group A occupancies not separated from one another in accordance with Section 707.3. 10 of the International Building Code shall be considered as a single occupancy for the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy.
Exception: {No change.}
Activation of fire alarm notification appliances shall:
1.
Cause illumination of the means of egress with light of not less than 1 foot-candle (11 lux) at the walking surface level, and
2.
Stop any conflicting or confusing sounds and visual distractions.
Section 907.2.3; change to read as follows:
[F] 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice/alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems.
Exceptions:
1.
{No change.}
1.1.
Residential In-Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2½ or less years of age, see Section 907.2.6.)
{No change to remainder of exceptions.}
Section 907.2.13, Exception 3; change to read as follows:
[F] 3. Open air portions of buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed areas.
Section 907.4.2; add Section 907.4.2.7 to read as follows:
[F] 907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type.
Section 907.6.1; add Section 907.6.1.1 to read as follows:
[F] 907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one foot vertical between supply and return circuit conductors.
The initiating device circuit (IDC) from a signaling line circuit interface device may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or less.
Section 907.6.3; delete all four Exceptions.
Section 909.22; add to read as follows:
[F] 909.22 Stairway or ramp pressurization alternative. Where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and the stair pressurization alternative is chosen for compliance with Building Code requirements for a smokeproof enclosure, interior exit stairways or ramps shall be pressurized to a minimum of 0.10 inches of water (25 Pa) and a maximum of 0.35 inches of water (87 Pa) in the shaft relative to the building measured with all interior exit stairway and ramp doors closed under maximum anticipated conditions of stack effect and wind effect. Such systems shall comply with Section 909, including the installation of a separate fire-fighter's smoke control panel as per Section 909.16, and a Smoke Control Permit shall be required from the Fire Department as per Section 105.7.
[F] 909.22.1 Ventilating equipment. The activation of ventilating equipment for the stair or ramp pressurization system shall be by smoke detectors installed at each floor level at an approved location at the entrance to the smokeproof enclosure. When the closing device for the stairway or ramp shaft and vestibule doors is activated by smoke detection or power failure, mechanical equipment shall activate and operate at the required performance levels. Smoke detectors shall be installed in accordance with Section 907.3.
[F] 909.22.1.1 Ventilation systems. Smokeproof enclosure ventilation systems shall be independent of other building ventilation systems. The equipment, control wiring, power wiring and ductwork shall comply with one of the following:
1.
Equipment, control wiring, power wiring and ductwork shall be located exterior to the building and directly connected to the smokeproof enclosure or connected to the smokeproof enclosure by ductwork enclosed by not less than 2-hour fire barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both.
2.
Equipment, control wiring, power wiring and ductwork shall be located within the smokeproof enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by not less than 2-hour barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both.
3.
Equipment, control wiring, power wiring and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by not less than 2-hour fire barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both.
Exceptions:
1.
Control wiring and power wiring utilizing a 2-hour rated cable or cable system.
2.
Where encased with not less than 2 inches (51 mm) of concrete.
3.
Control wiring and power wiring protected by a listed electrical circuit protective systems with a fire-resistance rating of not less than 2 hours.
[F] 909.22.1.2 Standby power. Mechanical vestibule and stairway and ramp shaft ventilation systems and automatic fire detection systems shall be provided with standby power in accordance with Section 2702 of the Building Code.
[F] 909.22.1.3 Acceptance and testing. Before the mechanical equipment is approved, the system shall be tested in the presence of the fire code official to confirm that the system is operating in compliance with these requirements.
Section 910.2; change Exception 2. and 3. to read as follows:
[F] 2. Only manual smoke and heat removal shall be required in areas of buildings equipped with early suppression fast-response (ESFR) sprinklers. Automatic smoke and heat removal is prohibited.
3. Only manual smoke and heat removal shall not be required in areas of buildings equipped with control mode special application sprinklers with a response time index of 50(m*S) 1/2 or less that are listed to control a fire in stored commodities with 12 or fewer sprinklers. Automatic smoke and heat removal is prohibited.
Section 910.2; add subsections 910.2.3 with exceptions to read as follows:
[F] 910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows:
1.
In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet (1394 m ) in single floor area.
Exception: Buildings of noncombustible construction containing only noncombustible materials.
2.
In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive materials as required for a high-hazard commodity classification.
Exception: Buildings of noncombustible construction containing only noncombustible materials.
Section 910.3; add section 910.3.4 to read as follows:
[F] 910.3.4 Vent operation. Smoke and heat vents shall be capable of being operated by approved automatic and manual means. Automatic operation of smoke and heat vents shall conform to the provisions of Sections 910.3.2.1 through 910.3.2.3.
[F] 910.3.4.1 Sprinklered buildings. Where installed in buildings equipped with an approved automatic sprinkler system, smoke and heat vents shall be designed to operate automatically. The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees F (approximately 38 degrees Celsius) greater than the temperature rating of the sprinklers installed.
Exception: Manual only system per 910.2
[F] 910.3.4.2 Nonsprinklered buildings. Where installed in buildings not equipped with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-responsive device rated at between 100°F (56°C) and 220°F (122°C) above ambient.
Exception: Listed gravity-operated drop out vents.
Section 912.2; add Section 912.2.3 to read as follows:
[F] 912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 feet of the fire department connection as the fire hose lays along an unobstructed path.
Section 913.1; add second paragraph and exception to read as follows:
[F] When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft. 8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1.
Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the fire code official. Access keys shall be provided in the key box as required by Section 506.1.
Section 1010.1.9.4 Bolt Locks; amend exceptions 3 and 4 as follows:
Exceptions:
3.
Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S occupancy. {Remainder unchanged}
4.
Where a pair of doors serves a Group A, B, F, M or S occupancy. {Remainder unchanged}
Section 1015.8 Window Openings; revise text as follows:
1.
Operable windows where the top of the sill of the opening is located more than 55 feet (16 764 mm) above the finished grade or other surface below and that are provided with window fall prevention devices that comply with ASTM F 2006.
Section 1101.1 Scope; add exception to Section 1101.1 as follows:
Exception: Components of projects regulated by and registered with Architectural Barriers Division of Texas Department of Licensing and Regulation shall be deemed to be in compliance with the requirements of this chapter.
Section 1203.1; amend to read as follows:
1203.1 General. Buildings shall be provided with natural ventilation in accordance with Section 1203.4, or mechanical ventilation in accordance with the International Mechanical Code.
Where air infiltration rate in a dwelling unit is 5 air changes or less per hour when tested with a blower door at a pressure 0.2 inch w.c. (50 Pa) in accordance with Section 402.4.1.2 of the International Energy Conservation Code, the dwelling unit shall be ventilated by mechanical means in accordance with Section 403 of the International Mechanical Code.
Table 1505.1; delete footnote c and replace footnote b with the following:
b.
Non-classified roof coverings shall be permitted on buildings of U occupancies having not more than 120 sq. ft. of protected roof area. When exceeding 120 sq. ft. of protected roof area, buildings of U occupancies may use non-rated non-combustible roof coverings.
c.
[delete]
Section 1505.7; delete the section
Section 1511.1; add a sentence to read as follows:
1511.1 General. Materials and methods of applications used for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15. All individual replacement shingles or shakes shall be in compliance with the rating required by Table 1505.1.
{text of exception unchanged}
Section 1704.2, Special inspections and tests; amended to read as follows:
1704.2 Special inspections and tests. Where application is made to the Building Official for construction as specified in Section 105, the owner or the owner's authorized agent, or the registered design professional in responsible charge, other than the contractor, shall employ one or more approved agencies to provide special inspections and tests during construction on the types of work listed under Section 1705 and identify the approved agencies to the Building Official. The special inspector shall not be employed by the contractor. These special inspections and tests are in addition to the inspections identified by the Building Official that are identified in Section 110.
Section 1704.2.1, Special inspector qualifications; amended to read as follows:
1704.2.1 Special inspector qualifications. Prior to the start of construction and or upon request, the approved agencies shall provide written documentation to the registered design professional in responsible charge and the building official demonstrating the competence and relevant experience or training of the special inspectors who will perform the special inspections and tests during construction. [Remainder unchanged]
Section 1704.2.4, Report requirement; amended to read as follows:
1704.2.4 Report requirement. Approved agencies shall keep records of special inspections and tests. The approved agency shall submit reports of special inspections and tests to the Building Official upon request, and to the registered design professional in responsible charge.
Individual inspection reports shall indicate that work inspected or tested was or was not completed in conformance to approved construction documents. [Remainder unchanged]
Section 1704.2.5.1, Fabricator approval; amended to read as follows:
1704.2.5.1 Fabricator approval. Special inspections during fabrications required by Section 1704 are not required where the work is done on the premises of a fabricator registered and approved to perform such work without special inspection. Approval shall be based upon review of the fabricator's written procedural and quality control manuals and periodic auditing of fabrication practices by an approved agency, or a fabricator that is enrolled in a nationally accepted inspections program. At completion of fabrication, the acceptable or approved fabricator shall submit a certificate of compliance to the owner or the owner's authorized agent or the registered design professional in responsible charge, stating that the work was performed in accordance with the approved construction documents. The certificate of compliance shall also be made available to the Building Official upon request.
Section 2902.1; add a second paragraph to read as follows:
In other than E Occupancies, the minimum number of fixtures in Table 2902.1 may be lowered, if requested in writing, by the applicant stating reasons for a reduced number and approved by the Building Official.
Table 2902.1; add footnote f to read as follows:
Table 2902.1
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES a, ff.
Drinking fountains are not required in M Occupancies with an occupant load of 100 or less, B Occupancies with an occupant load of 25 or less, and for dining and/or drinking establishments.
Section [P] 2902.6; change to read as follows:
[P] 2902.6 Small occupancies. Drinking fountains shall not be required for an occupant load of 25 or fewer.
Section 3002.1 Hoistway Enclosure Protection; add exceptions to read as follows:
Exceptions:
1.
Elevators wholly located within atriums complying with Section 404 shall not require hoistway enclosure protection.
2.
Elevators in open or enclosed parking garages that serve only the parking garage, and complying with Sections 406.5 and 406.6, respectively, shall not require hoistway enclosure protection.
Section 3005.7; add a Section 3005.7 as follows:
3005.7 Fire Protection in Machine rooms, control rooms, machinery spaces and control spaces.
3005.7.1 Automatic sprinkler system. The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, except as otherwise permitted by Section 903.3.1.1.1 and as prohibited by Section 3005.7.2.1.
3005.7.2.1 Prohibited locations. Automatic sprinklers shall not be installed in machine rooms, elevator machinery spaces, control rooms, control spaces and elevator hoist-ways.
3005.7.2.2 Sprinkler system monitoring. The sprinkler system shall have a sprinkler control valve supervisory switch and water-flow initiating device provided for each floor that is monitored by the building's fire alarm system.
3005.7.2.3 Water protection. An approved method to prevent water from infiltrating into the hoistway enclosure from the operation of the automatic sprinkler system outside the elevator lobby shall be provided.
3005.7.2.4 Shunt trip. Means for elevator shutdown in accordance with Section 3005.5 shall not be installed.
Section 3005.8; add Section 3005.8 as follows:
3005.8 Storage. Storage shall not be allowed within the elevator machine room, control room, machinery spaces and/or control spaces. Provide approved signage at each entry to the above listed locations stating: "No Storage Allowed."
Section 3006.2, Hoistway opening protection required; revise text as follows:
5.
The building is a high rise and the elevator hoistway is more than 55 feet (16 764 mm) in height. The height of the hoistway shall be measured from the lowest floor at or above grade to the highest floors served by the hoistway.
Section 3109.1; change to read as follows:
3109.1 General. Swimming pools shall comply with the requirements of sections 3109.2 through 3109.5 and other applicable sections of this code and complying with applicable state laws.
(Ord. No. 04-05, § 1(6-2), 1-20-2004; Ord. No. 07-02, § 1(6-2), 1-16-2007; Ord. No. 08-03, § 1(exh. A, art. I), 1-22-2008; Ord. No. 12-02, § 1, 2-6-2012; Ord. No. 13-26, § 1, 8-19-2013; Ord. No. 16-32, § 1, 5-16-2016)